Dimensions and Clearances ThermElect Hydronic Furnace

Hydronic Furnace

Storage Module (53kW and 80kW)

  • Back = 8 inches
  • Bottom = 1 inch (from combustible material)
  • Right Side = 12 inches
  • Top = 8 inches (from combustible material)
  • Left Side & Front = 36 inches (for ease in servicing)

Adhere to clearances and provide appropriate ventilation to maintain no greater than 85oF air temperature in area where unit is installed.

NOTE: Some electrical codes may require a greater front clearance depending on operating voltages and other factors.